beautypg.com

Aerco protonode gateway, User manual – AERCO ProtoNode Gateway Rev 3 (with external LEDs) User Manual

Page 109

background image

AERCO ProtoNode Gateway

User Manual

OMM-0080_0H

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 109 of 126

GF-129

Ph.: 800-526-0288

11/06/2014

Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master

Equip

Point Name

Name

Read

Only

BACnet
Type:ID

N2 Type

N2

ID

Lon SNVT

NAME

Lon

SNVT

Lon Direction

ModBus
Address

4

Air Temp

SMD_BAS_IP_HTR_04_[7]

AV:607

Data Float

113

nvoHTR_04_8 inc count (9)

Output (non-polled)

30607

4

Flame Strength

SMD_BAS_IP_HTR_04_[8]

AV:608

Data Float

114

nvoHTR_04_9 inc count (9)

Output (non-polled)

30608

4

Fire Rate In

SMD_BAS_IP_HTR_04_[9]

AV:609

Data Float

115

nvoHTR_04_10 inc count (9)

Output (non-polled)

30609

4

Fire Rate Out

SMD_BAS_IP_HTR_04_[10]

AV:610

Data Float

116

nvoHTR_04_11 inc count (9)

Output (non-polled)

30610

4

Unit Type

SMD_BAS_IP_HTR_04_[11]

AV:611

Data Float

117

nvoHTR_04_12 inc count (9)

Output (non-polled)

30611

4

Unit Size

SMD_BAS_IP_HTR_04_[12]

AV:612

Data Float

118

nvoHTR_04_13 inc count (9)

Output (non-polled)

30612

4

Value State

SMD_BAS_IP_HTR_04_[13]

AV:613

Data Float

119

nvoHTR_04_14 inc count (9)

Output (non-polled)

30613

4

Net Remote Setpt

SMD_BAS_IP_HTR_04_[14]

AV:614

Data Float

120

nvoHTR_04_15 inc count (9)

Output (non-polled)

30614

4

Run Cycles Upper

SMD_BAS_IP_HTR_04_[15]

AV:615

Data Float

121

nvoHTR_04_16 inc count (9)

Output (non-polled)

30615

4

Run Cycles Lower

SMD_BAS_IP_HTR_04_[16]

AV:616

Data Float

122

nvoHTR_04_17 inc count (9)

Output (non-polled)

30616

4

Run Hours Upper

SMD_BAS_IP_HTR_04_[17]

AV:617

Data Float

123

nvoHTR_04_18 inc count (9)

Output (non-polled)

30617

4

Run Hours Lower

SMD_BAS_IP_HTR_04_[18]

AV:618

Data Float

124

nvoHTR_04_19 inc count (9)

Output (non-polled)

30618

4

Oxygen Level

SMD_BAS_IP_HTR_04_[19]

AV:619

Data Float

125

nvoHTR_04_20 inc count (9)

Output (non-polled)

30619

Blr Addr 5

5

Comm Address

SMD_BAS_IP_HTR_05_[0]

AV:700

Data Float

126

nvoHTR_05_1 inc count (9)

Output (non-polled)

30700

5

Unit Status

SMD_BAS_IP_HTR_05_[1]

AV:701

Data Float

127

nvoHTR_05_2 inc count (9)

Output (non-polled)

30701

5

Fault Code

SMD_BAS_IP_HTR_05_[2]

AV:702

Data Float

128

nvoHTR_05_3 inc count (9)

Output (non-polled)

30702

5

Outlet Temp

SMD_BAS_IP_HTR_05_[3]

AV:703

Data Float

129

nvoHTR_05_4 inc count (9)

Output (non-polled)

30703

5

FFWD Temp

SMD_BAS_IP_HTR_05_[4]

AV:704

Data Float

130

nvoHTR_05_5 inc count (9)

Output (non-polled)

30704

5

Inlet Temp

SMD_BAS_IP_HTR_05_[5]

AV:705

Data Float

131

nvoHTR_05_6 inc count (9)

Output (non-polled)

30705

5

Exhaust Temp

SMD_BAS_IP_HTR_05_[6]

AV:706

Data Float

132

nvoHTR_05_7 inc count (9)

Output (non-polled)

30706

5

Air Temp

SMD_BAS_IP_HTR_05_[7]

AV:707

Data Float

133

nvoHTR_05_8 inc count (9)

Output (non-polled)

30707

5

Flame Strength

SMD_BAS_IP_HTR_05_[8]

AV:708

Data Float

134

nvoHTR_05_9 inc count (9)

Output (non-polled)

30708

5

Fire Rate In

SMD_BAS_IP_HTR_05_[9]

AV:709

Data Float

135

nvoHTR_05_10 inc count (9)

Output (non-polled)

30709

5

Fire Rate Out

SMD_BAS_IP_HTR_05_[10]

AV:710

Data Float

136

nvoHTR_05_11 inc count (9)

Output (non-polled)

30710