I722 – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 68
![background image](/manuals/580903/68/background.png)
2-34
LiquiFlo AC Drive, Software Reference Version 6.4
Step 11. Run the Drive
This step describes how to increase the speed reference across the speed range and
check for proper motor operation. This step assumes that P.000 is set to LOCL
(control is local) and the motor is connected to the load and power is turned back on.
Step 11.1 Press the START key.
The drive is now running and the
keypad/display is in monitor mode.
Step 11.2 Press the ▲
or ▼ key once. All monitor mode LEDs will turn off.
Increase the speed reference to the maximum value by using the
▲ key.
Wait five seconds or press the ENTER key to return to monitor mode.
This increases the drive speed reference
and the motor will rotate up to maximum
speed.
The monitor mode LEDs turn off when the
reference is changed.
The display now shows the actual drive
speed. Your speed display may be different.
0
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
i722
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
i722
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC