U.008 – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 63
![background image](/manuals/580903/63/background.png)
Starting Up the Drive for Vector Regulation
2-29
Step 8.4 Press the ENTER key.
After pressing ENTER, the same parameter
is displayed. You can now go to the next
step.
Step 8.5 Press the PROGRAM key twice to exit program mode.
The display flashes S-En. This reminds you
that the self-tuning procedure is enabled.
Step 8.6 Press the START key to begin the self-tuning procedure.
The display flashes S-Ac, indicating that the
self-tuning procedure is active.
This procedure takes a few minutes. S-Ac
flashes on the display until the procedure is
complete.
The motor should be rotating in the
counter-clockwise (CCW) direction when
viewed from the driven motor shaft end.
u.008
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
S-e
!
ATTENTION: The motor will rotate during the self-tuning procedure. Stay
clear of rotating machinery. Failure to observe this precaution could result
in severe bodily injury or loss of life.
ATTENTION: The motor must be uncoupled from the driven load during
the self-tuning operation or incorrect parameter values will result. This
includes any shaft-coupled devices, such as reducers, belts, and brakes.
Failure to observe this precaution could result in damage to, or
destruction of, the equipment.