Starting Up the Drive for Volts/Hertz Regulation

1-15

Step 5.12 Press the ▲

key to increase the motor nameplate amps, or the ▼ key to

decrease motor nameplate amps.

The adjustment range depends on the
drive rating. See Appendix C.

VALUE ENTERED:

Step 5.13 Press the ENTER key to save the changed value.

After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.

Step 5.14 Press the ▲

key to display H.003, Torque Boost Voltage.

This parameter is required to offset the
voltage drop of the motor at low speeds
and produce constant torque. For
example, high friction loads may require
high starting torque.

Refer to figure 4.11 for more
information.

Step 5.15 Press the ENTER key.

The default setting is 0.5.

h.002

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

h.003

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

0.5

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC