Troubleshooting the Drive Using Error Codes
5-5
OF
Overfrequency
Drive has exceeded maximum
allowable output frequency.
Regenerating energy is too high.
Stability or slip compensation circuit
adds frequency reference.
If H.016 ON, searching current is too
high. Motor is too small.
Vector: Check parameters Encoder
PPR (U.001), Motor Poles (U.002),
Base Frequency (U.003).
V/Hz: Check DC bus voltage; increase
decelerating time. Check values Max
Speed (P.004) / Overfreq. (H.022).
Check slip compensation (H.004).
If H.016 ON, check motor size versus
Power Module size, recheck setting of
P.005 (too high).
OH
Drive
overtemperature
Cooling fan failure.
Check ambient temperature, cooling
fan, minimum clearances around
drive.
OL
Motor overload
Excess motor current.
V/Hz: Torque boost too high, therm.
overload level too low.
Vector: Check actual/Motor Rated
Nameplate Amps (U.004)
V/Hz: Check actual current/Torque
Boost (H.003).
Check that Power Module is sized
correctly.
Reduce load on motor (for example, at
low frequency).
Excess load on motor, for example, at
too low speeds.
Check that Power Module is sized
correctly. Reduce load on motor (e.g.,
at low frequency).
Loss of phase connection.
Check output lines to the motor.
OPL
Motor output phase
loss
Phase lost between drive and motor.
Check connections and cable of all 3
phases and motor windings. Replace
any damaged cable.
OSP
Overspeed
(Vector only)
RPM above 130% Maximum Speed
(P.004), speed regulator response not
optimized.
Check Encoder PPR (U.001), Motor
Poles (U.002), Base Frequency
(U.003), Motor Nameplate RPM
Speed (U.005). Check Reg.
Proportional (U.012) Integral Gain
(U.013)
PUc
Missing Power
Module ID
connector
Bad or disconnected cable between
Regulator and Power Module.
Check cables between Regulator
board and Power Module.
PUn
Power Module not
identified
Drive parameters have been restored
to power-up defaults. Regulator has
not been configured to match Power
Module.
Power Module must be configured by
Reliance service personnel.
PUo
Drive power
electronic
overload
Power Module overloaded.
Too high DC Braking Current
(H.007) or Torque Boost (H.003).
Check load to Power Module.
Check Power Module sizing versus
application. Check DC Braking
Current value (H.007). Check Torque
Boost (H.003).
SF
Self-tuning status
(Vector only)
See parameter U.009
SrL
Communication
loss between
Regulator/PC/OIM
Serial port communication cable, PC
or OIM communication port setup.
Check connection cable and
communication port setup.
Table 5.2 – List of Fault Codes (Continued)
Code
Fault
Description
Fault Cause
Corrective Action