4-60

LiquiFlo AC Drive, Software Reference Version 6.4

Operating a motor continuously at a particular frequency may cause vibrational
resonance within some machines. Three independent parameter pairs can be
configured for avoidance frequency and frequency band to prevent motor vibration by
preventing the drive output frequency from operating within the selected band(s).
Refer to figure 4.12.

The actual avoidance frequency selection is limited by Minimum Speed (P.003) and
Maximum Speed (P.004). Normal acceleration and deceleration is not affected by this
function.

H.009 Avoidance Frequency Enable

This parameter
enables the
avoidance frequency
bands selected in
H.011, H.013, and
H.015.

Parameter Range:

OFF = Disable avoidance frequency processing

ON = Enable avoidance frequency processing

Default Setting:

OFF

Parameter Type:

Tunable

Refer also to parameters:

P.003 Minimum Speed
P.004 Maximum Speed
H.010 to H.015 Avoidance Frequency Midpoint and

Band 1, 2, and 3

Figure 4.12 – Avoidance Frequency Band

Max Hz

AF 3

AF 2

AF 1

Avoidance
Frequency Band

Output
Frequency

Speed Reference

Min

Max

Min Hz

Base Frequency