beautypg.com

Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual

Page 67

background image

Starting Up the Drive for Vector Regulation

2-33

Step 10.8 Visually check that the motor rotates counter-clockwise (CCW) when

viewed from the driven motor shaft end.

Step 10.9

If the rotation direction is NOT correct, press the STOP/RESET key and continue
with step 10.10.

If the rotation direction is correct, continue with step 10.14.

When the STOP/RESET key is pressed, the
RUNNING LED turns off.

Step 10.10 Turn off and lock out or tag power to the drive.

Step 10.11 Verify that the DC bus capacitors are discharged. Refer to the hardware

reference manual for this procedure.

Step 10.12 Switch any two of the motor leads (U, V, or W) and A and A NOT on the

encoder.

Step 10.13 Turn power on, and press the START key. Repeat step 10.8.

Step 10.14 To make sure the drive is not inadvertently started, turn off and lock out

or tag power to the drive. Verify that the motor direction is appropriate
for the required machine direction, and then connect the motor to the
load.

CCW

0

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

!

ATTENTION: DC bus capacitors retain hazardous voltages after input
power has been disconnected. After disconnecting input power, wait five
(5) minutes for the DC bus capacitors to discharge and then check the
voltage with a voltmeter to ensure the DC bus capacitors are discharged
before touching any internal components. Failure to observe this
precaution could result in severe bodily injury or loss of life.