The value entered should be within 10% of actual line voltage. If this parameter is set
too low, it may cause a drive fault on overvoltage.

If actual frequency exceeds the set value, the inverter will fault (OF will be displayed
on the keypad/display) and the drive will stop.

The overfrequency limit should be set approximately 15 Hz above Maximum Speed
(P.004).

H.021 AC Line Volts

This parameter is the
phase-to-phase line
voltage provided to
the drive input power
terminals.

Parameter Range:

300 to 565 VAC

Default Setting:

460

Parameter Type:

Configurable

Refer also to parameters:

N/A

H.022 Overfrequency Limit

This parameter
provides overspeed
protection by setting
the fault level for
maximum frequency
output.

Parameter Range:

30.0 to 4 x H.001 + 5% or 210 Hz

*

Default Setting:

90.0

Parameter Type:

Configurable

Refer also to parameters:

P.004 Maximum Speed

*

Drive will use the lesser value.

!

ATTENTION: The user is responsible for ensuring that driven machinery,
all drive-train mechanisms, and application material are capable of safe
operation at the overfrequency limit. Failure to observe this precaution
could result in bodily injury.