Starting Up the Drive for Volts/Hertz Regulation

1-17

Step 5.19 Press the ENTER key.

The default setting is 0.

Step 5.20 Press the ▲ key to increase the selection value, or leave it at 0.

If you do not have AC input or you are using a snubber resistor, see the

H.017 parameter description for more informaton.

The adjustment range is:

0 = AC input; snubber resistor not used;

ride-through enabled.

1 = AC input; snubber resistor used;

ride-through enabled.

2 = DC input; snubber resistor not used;

ride-through disabled.

3 = DC input; snubber resistor used;

ride-through disabled.

4 = DC input; snubber resistor not used;

ride-through enabled.

5 = DC input; snubber resistor used;

ride-through enabled.

VALUE ENTERED:

Step 5.21 Press the ENTER key to save the value.

After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.

0

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

0

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

h.0i7

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC