H.0i7 – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 27

Starting Up the Drive for Volts/Hertz Regulation
1-17
Step 5.19 Press the ENTER key.
The default setting is 0.
Step 5.20 Press the ▲ key to increase the selection value, or leave it at 0.
If you do not have AC input or you are using a snubber resistor, see the
H.017 parameter description for more informaton.
The adjustment range is:
0 = AC input; snubber resistor not used;
ride-through enabled.
1 = AC input; snubber resistor used;
ride-through enabled.
2 = DC input; snubber resistor not used;
ride-through disabled.
3 = DC input; snubber resistor used;
ride-through disabled.
4 = DC input; snubber resistor not used;
ride-through enabled.
5 = DC input; snubber resistor used;
ride-through enabled.
VALUE ENTERED:
Step 5.21 Press the ENTER key to save the value.
After pressing ENTER, the same
parameter is displayed. You can now
move to the next parameter.
0
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
0
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
h.0i7
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC