Ppendix, Power module-dependent parameter default values – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 193
Power Module-Dependent Parameter Default Values
C-1
A
PPENDIX
C
Power Module-Dependent
Parameter Default Values
Second Menu General Parameters (USA Defaults)
Second Menu Volts/Hertz Parameters (USA Defaults)
Second Menu Vector Parameters (USA Defaults)
Parameter
Number
Parameter Name
B-Frame
C-Frame
D-Frame
41L4060
41LR4060
50LW4060
50LR4060
64LW4060
64LR4060
120L4060
P.047
Carrier Frequency (kHz)
2
2
2
2
Parameter
Number
Parameter Name
B-Frame
C-Frame
D-Frame
41L4060
41LR4060
50LW4060
50LR4060
64LW4060
64LR4060
120L4060
H.002
Motor Nameplate Amps
386.0
500.0
643.0
1157.0
Parameter
Number
Parameter Name
B-Frame
C-Frame
D-Frame
41L4060
41LR4060
50LW4060
50LR4060
64LW4060
64LR4060
120L4060
U.004
Motor Nameplate Amps
386.0
500.0
643.0
1157.0
U.005
Motor Nameplate RPM
1785
1785
1785
1785
U.006
Magnetizing Current
35.0
35.0
35.0
35.0
U.012
Speed Regulator Proportional Gain
10.00
10.00
10.00
10.00
U.013
Speed Regulator Integral Gain
5.00
5.00
5.00
5.00
U.014
Torque Regulator Proportional Gain
0.20
0.20
0.20
0.20
U.015
Torque Regulator Integral Gain
100.0
100.0
100.0
100.0
U.016
Field Weakening Start RPM
1785
1785
1785
1785
U.017
Motor Top Speed
1785
1785
1785
1785
U.019
Flux Current Regulator Proportional
Gain
0.15
0.15
0.15
0.15
U.021
Rotor Time Constant
350
350
350
350
U.022
Motor Nameplate HP
350.0
450.0
600.0
1000.0
U.032
SVC Flux Current Regulator Gain
350
300
300
300