Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 200

E-2
LiquiFlo AC Drive, Software Reference Version 6.4
Summary of Options for P.007, P.008, and r.030
Option Comparison Tables
P.007 Options
P.008 Options
DIGIN 6
DIGIN 7
DIGIN 8
DIGIN 6
DIGIN 7
DIGIN 8
0 =
FWD/REV
RAMP 1/2
REM/LOC
0 =
Not used
Not used
Not used
1 =
Not used
FWD/REV
RAMP 1/2
1 =
MOP
↑
MOP
↓
Not used
2 =
Not used
FWD/REV
REM/LOC
2 =
2 Presets
Not used
Not used
3 =
Not used
RAMP 1/2
REM/LOC
3 =
4 Presets
Not used
4 =
Not used
Not used
FWD/REV
4 =
8 Presets
5 =
Not used
Not used
RAMP 1/2
5 =
Analog ref
and 1 preset
Not used
Not used
6 =
Not used
Not used
REM/LOC
7 =
Not used
Not used
Not used
6 =
Analog ref and 3 presets
Not used
8 =
FWD/REV
TRQ/SPD
REM/LOC
7 =
Analog ref and 7 presets
9 =
Not used
TRQ/SPD
REM/LOC
10 =
Not used
TRQ/SPD
FWD/REV
11 =
Not used
TRQ/SPD
RAMP 1/2
12 =
Not used
Not used
TRQ/SPD
r.030 Options
RMI DIGIN 1
RMI DIGIN 2
RMI DIGIN 3
RMI DIGIN 4
0 =
Ref 1/2
A/F
Aux 2
Aux 1
1 =
Ref 1/2
A/F
Aux 2
PI Enable
2 =
Ref 1/2
MOP
↑
MOP
↓
Aux 1
3 =
Ref 1/2
MOP
↑
MOP
↓
PI Enable
4 =
Ref 1/2
2 Presets
Aux 2
Aux 1
5 =
Ref 1/2
2 Presets
Aux 2
PI Enable
6 =
Ref 1/2
4 Presets
4 Presets
Aux 1
7 =
Ref 1/2
4 Presets
4 Presets
PI Enable
8 =
Ref 1/2
8 Presets
8 Presets
8 Presets
If P.007 =
Acceptable
P.008
Values
If r.030 =
Acceptable
P.008
Values
If P.008 =
Acceptable
P.007
Values
If P.008 =
Acceptable
r.030
Values
0
0
0
0-6 (all)
0
0-12 (all)
0
0-8 (all)
1
0, 2, 5
1
0-6 (all)
1
4-7, 12
1
0, 1, 4-8
2
0, 2, 5
2
0, 2-6
2
1-7, 9-12
2
0-3
3
0, 2, 5
3
0, 2-6
3
4-7, 12
3
0-3
4
0-3, 5, 6
4
0, 1
4
7
4
0-3
5
0-3, 5, 6
5
0, 1
5
1-7, 9-12
5
0-3
6
0-3, 5, 6
6
0, 1
6
4-7, 12
6
0-3
7
0-7 (all)
7
0, 1
7
7
7
0-3
8
0
8
0, 1
9
0, 2, 5
10
0, 2, 5
11
0, 2, 5
12
0-3, 5, 6