beautypg.com

I722, U.005 – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual

Page 56

background image

2-22

LiquiFlo AC Drive, Software Reference Version 6.4

Step 6.23 Press the ▲

key to display U.005, Motor Nameplate RPM.

This parameter is the Motor Nameplate
RPM and is taken from the motor
nameplate.

Step 6.24 Press the ENTER key to display the default setting of U.005.

This displays the Motor Nameplate RPM
setting. The default depends on the HP
rating of the Power Module. The display
shown here is only an example.

Step 6.25 Press the ▲

key to increase the motor nameplate RPM or the ▼ key to

decrease the motor nameplate RPM.

The adjustment range for this value
depends on the settings of U.002 (Motor
Poles) and U.003 (Motor Nameplate Base
Frequency).

VALUE ENTERED:

!

ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002
(Motor Poles), U.003 (Motor Nameplate Base Frequency), U.005 (Motor
Nameplate RPM), and U.017 (Motor Top Speed) determines the motor
maximum speed. These parameters must be set by a qualified person
who understands the significance of setting them accurately. Failure to
observe this precaution could result in bodily injury.

u.005

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC

i722

Forward
Reverse

AUTO

MAN

ENTER

RUN
JOG

PROGRAM

START

STOP

RESET

SPEED
VOLTS

AMPS

Hz

Kw

TORQUE

Password

RUNNING

REMOTE

JOG

AUTO

FORWARD

REVERSE

PROGRAM

RELIANCE

ELECTRIC