2-22
LiquiFlo AC Drive, Software Reference Version 6.4
Step 6.23 Press the ▲
key to display U.005, Motor Nameplate RPM.
This parameter is the Motor Nameplate
RPM and is taken from the motor
nameplate.
Step 6.24 Press the ENTER key to display the default setting of U.005.
This displays the Motor Nameplate RPM
setting. The default depends on the HP
rating of the Power Module. The display
shown here is only an example.
Step 6.25 Press the ▲
key to increase the motor nameplate RPM or the ▼ key to
decrease the motor nameplate RPM.
The adjustment range for this value
depends on the settings of U.002 (Motor
Poles) and U.003 (Motor Nameplate Base
Frequency).
VALUE ENTERED:
!
ATTENTION: The setting of parameters U.001 (Encoder PPR), U.002
(Motor Poles), U.003 (Motor Nameplate Base Frequency), U.005 (Motor
Nameplate RPM), and U.017 (Motor Top Speed) determines the motor
maximum speed. These parameters must be set by a qualified person
who understands the significance of setting them accurately. Failure to
observe this precaution could result in bodily injury.
u.005
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC
i722
Forward
Reverse
AUTO
MAN
ENTER
RUN
JOG
PROGRAM
START
STOP
RESET
SPEED
VOLTS
AMPS
Hz
Kw
TORQUE
Password
RUNNING
REMOTE
JOG
AUTO
FORWARD
REVERSE
PROGRAM
RELIANCE
ELECTRIC