P.044 fault auto reset time – Rockwell Automation Liqui-Flo AC GP Vector Drive Version 6.4 User Manual
Page 119

Programming Reference
4-37
P.043 Fault Auto Reset Attempts
(continued)
Table 4.5 lists the faults that can be auto reset:
All other faults cannot be auto reset.
Note that the auto reset feature will be disabled during the vector self-tuning operation
and the V/Hz identification procedure.
After the drive has detected the fault and is counting down the auto-reset time period,
the display will flash the countdown period in seconds in the following format:
"Ar30...Ar29...Ar28.........Ar01...Ar00"
If during this countdown, the operator presses the keypad STOP/RESET key, or
asserts the fault reset from the selected control source, the auto-reset countdown will
stop, and all faults will be reset.
Table 4.5 – Faults That Can Be Auto Reset
Fault Code
Description
AIn
4 to 20 mA analog input signal loss
bYC
DC bus charging bypass contactor
EC
Earth current failure (ground fault)
HIL
High line voltage
HU
High DC bus voltage
LU
Low DC bus voltage
nCL
Network communications loss
OH
Drive overtemperature
UbS
Asymmetrical bus charge
P.044 Fault Auto Reset Time
This parameter
specifies the amount
of time the drive will
wait to attempt to
reset drive faults.
Parameter Range:
1 to 60 seconds
Default Setting:
8
Parameter Type:
Configurable
Refer also to parameters:
P.043 Fault Auto Reset Attempts