Connect dc power – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 63
Publication 2711-UM014G-EN-P - September 2008
63
Applying Power and Resetting Terminal Chapter 2
Connect DC Power
The L1 versions (Cat. No. 2711-K5 A5 A18...32V1L1, 2711-T9C1L1) of
the PV300, PV300 Micro, PV550, PV600, PV900, and PV1000 terminals
connect to a 24V DC power source.
The table below shows the electrical ratings for the DC versions of the
terminals. Electronic circuitry and an internal fuse protect the
terminals from reverse polarity and over-voltage conditions.
Terminal Type
Supply Voltage
(24V DC nominal)
Power Consumption, Max
PV300 Micro
11...30V DC
2.5 W (0.105 A @ 24V DC)
PV300
18...32V DC
6 W (0.25 A @ 24V DC)
PV550
18...30V DC
18 W (0.75 A @ 24V DC)
PV550 (touch only)
18...32V DC
18 W (0.75 A @ 24V DC)
PV600
18...32V DC
24 W (1.0 A @ 24V DC)
PV600 (touch only)
18...32V DC
24 W (1.0 A @ 24V DC)
PV900M
18...30V DC
58 W (2.5 A @ 24V DC)
PV900C
18...32V DC
50 W (2.1 A @ 24V DC)
PV1000G
18...32V DC
24 W (1.0 A @ 24V DC)
PV1000C
18...32V DC
24 W (1.0 A @ 24V DC)
ATTENTION
Do not connect a DC rated PanelView terminal to an AC power
source. Connecting to an AC power source may damage the
terminal.
IMPORTANT
The PanelView terminals are designed for use when installed in
a NEMA Type 12, 13, NEMA 4X (indoor use only), IP54 or IP65
rated enclosure.
ATTENTION
Do not power PanelView terminals from the I/O power on a
controller or from DeviceNet network power. If you try to do
this, the PanelView will not power up and the DeviceNet or
controller power supply may be over-stressed.
ATTENTION
Use only a safety extra-low voltage (SELV) power supply as a
source for the PanelView 300 Micro, PanelView 300 or 550
touch screen terminal. A SELV power supply does not exceed
42.4V DC.