10 - installing the pv900/1000 terminals, Chapter objectives, Hazardous location considerations – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 161: Chapter 10, Installing the pv900/1000 terminals, Chapter

161
Publication 2711-UM014G-EN-P - September 2008
161
Chapter
10
Installing the PV900/1000 Terminals
Chapter Objectives
This chapter describes how to mount the PV900 and PV1000 terminals
in a panel or enclosure including:
•
hazardous locations and enclosures
•
required tools
•
mounting dimensions
•
clearances
•
cutout dimensions
•
installing the PV900/PV1000 terminal in a panel
Hazardous Location
Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D; or non-hazardous locations only. PV 1000 terminals are also
suitable for use in Class II, Division 2, Groups F, G, Class III, or
non-hazardous locations. The following WARNING statement applies
to use in hazardous locations.
See the nameplate on terminal for hazardous locations certifications.
WARNING
EXPLOSION HAZARD
•
Substitution of components may impair suitability for Class I, Class
II, Class III Division 2.
•
Do not replace components or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
•
Do not connect or disconnect components unless power has been
switched off or the area is known to be non-hazardous.
•
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be
protected by conduit or other means.
•
All wiring must comply with N.E.C. article 501-4(b), 502-4(b),
503-3(b) as appropriate.
ATTENTION
In Class I, Class II, Class III Division 2 Hazardous locations,
the PanelView 900/1000 terminals must be wired per the
National Electric Code as it applies to hazardous locations.
Peripheral equipment must also be suitable for the location in
which it is installed.