Connect ac power – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 61

Publication 2711-UM014G-EN-P - September 2008
61
Applying Power and Resetting Terminal Chapter 2
Connect AC Power
Below are AC electrical ratings for the PanelView terminals. The
PV550/PV600 touch screen only terminal is available only with DC
power, not AC power.
The PanelView terminals are IEC 1131-2 Equipment Class I devices
and require you to connect the GND (Ground) or
(Protective
Earth) terminal to an earth conductor.
Follow these steps to connect power to the AC versions of the
PanelView.
1. Secure AC power wires to the L1 and L2N terminal block screws.
2. Secure the Earth Ground/Protective Earth wire to the GND or
the
screw on the terminal block.
3. Apply power to the terminal.
Terminal Type
Supply Voltage
Power Consumption,
Max
PV550
85…264V AC, 47…63 Hz
45 VA
PV600
85…264V AC, 43…63 Hz
60 VA
PV900M/PV900C
85…264V AC, 47…63 Hz
110 VA
PV1000G/PV1000C
85…264V AC, 47…63 Hz
55 VA
PV1400
85…264V AC, 43…63 Hz
200 VA
ATTENTION
Do not apply power to the PanelView terminal until all wiring
connections have been made. Failure to do so may result in
electrical shock.
IMPORTANT
The PanelView terminals are designed for safe use when
installed in a NEMA Type 12, 13, 4X (indoor use only), IP54 or
IP65 rated enclosure.
ATTENTION
Improper wiring of the power terminals may result in
voltage at the communication connector shells.
See the appropriate wiring diagram on page 62.