Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 252
252
Publication 2711-UM014G-EN-P - September 2008
Appendix B Messages, Codes and Self-test Numbers
341
Proceed with
download?
0 or F1 -Abort
1 or F2 - Continue
Warning
You pressed [F2], Restore From Card
on the Memory Card configuration
screen.
Enter appropriate response:
0 or F1 to abort
1 or F2 to continue
342
The PVA File
exists.
0 or F1 -Abort
1 or F2 - Upload
with new PVA
filename
Reminder / File
Transfer Status
You pressed [F3], Save To Card on the
Memory Card configuration screen
when the file exists on the card.
Enter appropriate response:
0 or F1 to abort
1 or F2 to upload new PVA file.
361
Value not in
range
Reminder
Entered value is outside of valid
range.
Enter a value within the valid range.
364
Closing Files...
Status
Terminal is preparing for removal of
memory card.
Wait for files to close before
removing memory card.
365
Remove card...
Reminder
You must remove the memory card for
the terminal to continues operation.
Remove the memory card.
366
Card
disconnection
will require card
removal to
continue
operation.
Warning
Attempt to disconnect the memory
card.
After memory card is disconnected it
must be removed from card slot
before the terminal will operate.
392
File not
supported
Reminder/File
Transfer Status
File is incompatible with the terminal
type.
In PanelBuilder32, select the Setup
tab on the Application Settings dialog
and select the correct terminal type.
393
File not
supported
Reminder/File
Transfer Status
File is incompatible with the
communication protocol of the
terminal.
In PanelBuilder32, select the Setup
tab on the Application Settings dialog
and make sure the protocol matches
your terminal.
394
File not
supported
Reminder/File
Transfer Status
File is incompatible with the
terminal’s firmware.
In PanelBuilder32, click the Catalog &
Revisions button on the Setup tab on
the Application Settings dialog.
Select a firmware version that
matches your terminal.
395
File not
supported
Reminder/File
Transfer Status
File is incompatible with the operator
input type (keypad, touch or keypad
and touch) of terminal.
In PanelBuilder32, select the Setup
tab on the Application Settings
dialog. Select the type of operator
input that matches your terminal.
396
File not
supported
Reminder/File
Transfer Status
File is incompatible with the terminal. Download the file to the terminal
again. If problem reoccurs, contact
technical support.
415
Retained memory
lost.
Presets were
loaded.
Reminder
The battery backed memory was
invalid during startup. The system
defaulted to preset values instead of
the last states.
No action necessary. Terminal reverts
to defaults.
Error Number
Terminal
Messages
Type
Meaning
Recommended Action