Chapter 6 Installing the PV300 Micro Terminal
Use only the following communication cables in Class 1, Division 2,
Hazardous Locations.
Enclosures
Mount the PanelView 300 Micro terminal in a panel or enclosure to
protect the internal circuitry. The terminal meets NEMA 12/13, 4X
(indoor use), IP54 or IP65 ratings only when properly mounted in a
panel or enclosure with the equivalent rating. Allow enough space
within the enclosure for adequate ventilation. Consider heat produced
by other devices in the enclosure. The ambient temperature around
the PanelView 300 Micro terminal must be° between 0…55 °C
(32…131 °F).
Make provisions for accessing the side panel of the terminal for
wiring, maintenance and troubleshooting.
Required Tools
Other than the tools required to make panel or enclosure cutouts,
these tools are required for installation.
•
7 mm (M4) deep-well socket wrench or nut driver
•
small slotted screwdriver
•
torque wrench (lb-in)
Mounting Dimensions
Environmental Classification
Communication Cable
Class I, Division 2, Hazardous
Locations
1761-CBL-PM01, Series C
1761-CBL-HM02, Series C
1761-CBL-AM00, Series C
1761-CBL-AP00, Series C
2711-CBL-PM05, Series C
2711-CBL-HM05, Series C
2711-CBL-PM10, Series C
2711-CBL-HM10, Series C
133 mm
(5.23 in.)
111 mm
(4.38 in.)
35 mm
(1.39 in.)
48 mm
(1.87 in.)