Appendix B Messages, Codes and Self-test Numbers
Error Number
Terminal
Messages
Type
Meaning
Recommended Action
xx,xx,xx
Number depends
on hardware fault
detected.
Communication
Interface Fault
Critical Fault
A hardware problem was detected
during power-up. If you ignore
message and display the EtherNet/IP
Communication Screen, the Comm
Status displays “Comms hardware
fault:” without an error number. The
FW revision, serial number and
EtherNet/IP address fields are
displayed.
Contact technical support to have unit
repaired.
770
Buffer overflow
Comm Status
Internal error occurred.
Contact technical support.
771
Buffer underflow
Comm Status
Internal error occurred.
Contact technical support.
1799 Heap
partition
empty
Comm Status
Internal error occurred.
Contact technical support.
16387
Comms not
started yet...
Comm Status
The PanelView has not connected to
the network.
Check IP configuration (on the
Communication Setup screen) and
wait for PanelView to connect to the
network.
16388
CIP S/N is not
valid
Critical fault.
DC incorrectly configured.
Contact technical support.
16389
Out of buffers
Critical fault.
No buffers are available for read or
write operations.
Contact technical support.
16390
An initial write
failed
Comm Warning
Write to Logic Controller on Startup
was configured and on powerup, the
PanelView could not write initial
values to a node's data table address.
or
Write to Logic Controller on Startup
was not configured and the
PanelView was unable to write a
controller. Note: The error is only
displayed on the first write attempt.
Check/define data table address in
the controller.
Check communication connections
and node configuration in the
application.
16391
PV write failed
Comm Warning
PanelView is communicating with the
controller. The data table address
does not exist.
Check/define data table address in
the controller.
16392
PV write timeout
Comm Warning
PanelView is not communicating with
the logic controller.
Check connections and node
configuration in the application.
16393
PV read fail
Comm Warning
PanelView is communicating with the
controller. The data table address
does not exist.
Check/define data table address in
the controller.
16394
PV read timeout
Comm Warning
PanelView is not communicating with
the controller.
Check/define data table address in
the controller.
16397
CN object
received a reset
request
Comm Warning
An Ethernet object received a reset
request from a device on the network.
The PanelView does not support
network resets.