Chapter 11 Installing the PV1400 Terminal

7. Install the self-locking nuts hand tight.

8. Alternately tighten the self-locking nuts (use 3/8 in. socket) until

the PV1400 terminal is held firmly against the panel.

The recommended tightening sequence is shown below.

The studs have an integral spacer that prevents the gasket from
being over-compressed. The amount of torque required
increases significantly as the gasket reaches the proper
compression. Tighten nuts to a torque of 1.13 Nm (10 lb-in.).

ATTENTION

Tighten mounting nuts to a torque of 1.13 Nm (10 lb-in.)
to provide a proper seal and prevent potential damage to
the terminal. Allen-Bradley assumes no responsibility for
water or chemical damage to the terminal or other
equipment within the enclosure because of improper
installation. A properly installed terminal has a small
gap between the bezel and enclosure.

1

5

13

9

18

16

15

4

3

7

8

12

11

2

6

14

10

17

1

2

9

10

5

6

4

3

7

8

12

11

Recommended Torque
Sequence Keypad
Terminals

Recommended
Torque Sequence
Touch Terminals

Note the sequence starts at center studs and continues to the corner studs.