Chapter 13 Troubleshooting and Maintenance
Remote I/O Status Indications
Status
Indicator
This pattern
Indicates
Comm
(1)
(1)
Comm Status indicator stays on until powerup self-test are complete
Solid Fill
Normal operating state (no communication faults)
No Fill
Communication not functioning
•
Verify that baud rate and rack settings match
the PLC settings
•
Verify proper terminal to controller connections
•
Verify that the PLC enables remote I/O
communication
Blinking
No communication established. PLC is in program
mode.
Flashing
When power is first applied (momentarily)
Fault
No Fill
Normal operating state
Solid Fill
Fault detected. Cycle power to the terminal. If the
fault still exists, the terminal requires servicing.
Blinking
Hardware is functioning but no application is
loaded or the current application is corrupt.
DeviceNet, ControlNet, and EtherNet/IP Network Indicators
Status
Indicator
This Pattern
Indicates
Comm
Solid Fill
Normal operating state (no communication faults).
No Fill
Hardware failed.
Flashing
When power is first applied (momentarily).
Blinking
No communication established.
Fault
Solid Fill
Hardware failed.
No Fill
Normal operating state (no communication faults).
Blinking
Hardware is functioning but no application is
loaded or the current application is corrupt.