Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 253

Publication 2711-UM014G-EN-P - September 2008
253
Messages, Codes and Self-test Numbers Appendix B
436
Logic Controller
has screen
control
Reminder
You tried to change the application
screen but it is configured for
controller only access.
No action required, controller will
change screens as programmed.
634
Read Fail or
Write Fail
Status
ControlLogix Tag or address does not
exist or is the wrong data type.
Designated slot does not contain a
ControlLogix Processor.
Check tag address.
Check for data type mismatch.
Verify ControlLogix slot location.
1109
Font file
unavailable,
Font error = ****
Minor Fault or
Terminal Fault
You downloaded an application to the
PanelView without the appropriate
memory card (containing the font file)
inserted in the card slot of the
terminal.
From the Memory Card screen, press
the Disconnect button to close the
files on the card. Remove the card
from the card slot. Locate the card
containing the font file or copy the
correct font file to a card. Insert the
correct memory card in the card slot
and enter Run mode.
1110
No valid
application
Reminder
You tried to run an application that
has not been downloaded to the
terminal.
Download application to terminal.
1118
Access denied.
Status
Wrong password entered.
Enter a valid password.
1119
Access denied.
Status
Password not recognized
Enter a valid password.
1120
Security
tampering.
Status
PVA file was corrupted - attempt to
bypass security was detected
New application file must be
downloaded to the terminal.
1121
No operator
selected.
Status
There is no currently selected
operator, but a password change has
been requested
Select the operator requiring the new
password.
1122
Password change
is not allowed.
Reminder
Password is unchangeable
Password cannot be changed at the
current level of security.
1123
Password change
is not allowed.
Reminder
Operator cannot change password
Current operator does not have
access for password changes.
1124
New password
must be entered
before it can be
verified.
Reminder
New pass words must be entered
twice.
Enter the new password again to
verify that it was entered correctly.
1125
New and verify
passwords differ.
Status
The same password was not entered
for verification.
Enter the same password for New
and Verify.
1126
Please verify new
password.
Reminder
New pass words must be entered
twice.
Enter the new password again.
1127
Password
changed
Reminder
Password change is effective.
You must use new password for
security access.
2005
Application file:
Insufficient RAM
Terminal Fault
Application file may be too large.
Try again. If possible, reduce the size
of the application.
2007 - 2010
Application file
contains errors
Terminal Fault
Application contains incompatible
data.
Check application and try again.
Error Number
Terminal
Messages
Type
Meaning
Recommended Action