General codes controlnet codes – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 262

262
Publication 2711-UM014G-EN-P - September 2008
Appendix B Messages, Codes and Self-test Numbers
General Codes
ControlNet Codes
These errors appear at the top of the application screen or on the
terminal’s configuration screen. If you should get an alert number that
is not listed, contact technical support.
General
Terminal
Alert Code
Alert Type
Indicates
Recommended Action
603
Critical fault
File download error
Reset the terminal. If problem occurs again, contact
technical support.
9020
Critical fault
An internal fault occurred.
Reset the terminal. If problem occurs again, contact
technical support.
ControlNet
Error Codes
Error Type
Indicates
Recommended Action
1803
Informational
The communication device has
completed the request to force
the device into the listen-only
state.
The PanelView was detected as having a duplicate
node address and is in the listen-only mode. Check
the node address (MAC ID) of the devices on the
network to verify that addresses are not duplicated.
1824
Warning
The PanelView was forced to a
listen-only state.
Contact technical support.
1826
Warning
A fixed tag packet was received
but there is no place to route the
packet. The data packet is
discarded and the error message
is displayed.
Contact technical support.
1828
Warning
An attempt was made to open
an unsupported transport class.
Contact technical support.
1829
Warning
An attempt was made to open a
Class 1 transport with
application triggering or a Class
3 transport with cyclic
triggering.
Contact technical support.
3333
Warning
A connection has timed out.
A file transfer was unexpectedly interrupted. Try to
transfer again.