11 - installing the pv1400 terminal, Chapter objectives, Enclosures – Rockwell Automation 2711 Standard PanelView Operator Terminal User Manual User Manual
Page 169: Required tools, Chapter 11, Installing the pv1400 terminal, Chapter objectives enclosures required tools, Chapter

169
Publication 2711-UM014G-EN-P - September 2008
169
Chapter
11
Installing the PV1400 Terminal
Chapter Objectives
This chapter describes how to mount the PV1400 terminal in a panel
or enclosure including:
•
enclosures
•
recommended tools
•
mounting dimensions
•
clearances
•
cutout dimensions
•
installing the PV1400 terminal in a panel
Enclosures
The PV1400 terminal must be mounted in an environment that
provides IEC-1131-2 Pollution degree 2 protection.
Mount the PV1400 terminal in a panel or enclosure to protect the
internal circuitry. The terminal meets NEMA Type 12/13 and 4X
(indoor use) ratings only when mounted in a panel or enclosure with
the equivalent rating.
Allow enough space within the enclosure for adequate ventilation.
Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminals must be between 0…55 °C
(32…131 °F).
Make provisions to access the back sides of the terminal. Access is
required for wiring, routine maintenance, adjusting
brightness/contrast, installing a memory card and troubleshooting.
Required Tools
In addition to the tools required to make the panel cutout, you need
the tools below.
For clip mounting:
•
socket screwdriver (phillips head or slotted)
•
406 mm (16 in.) extension rod (minimum)
•
socket driver (in/lab torque wrench recommended)
IMPORTANT
PanelView 1400 terminals are no longer available. Contact your
local sales office or authorized Rockwell Distributor for suitable
substitutes.