Save configuration – Rockwell Automation 5370 CVIM Communications Manual User Manual
Page 84

Chapter 5
Using the RS–232 Ports
5–14
Numerical Results Block Returned Data Format
[CR] [LF]
61_01_04_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00~00_[CR][LF]
00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00~00_[CR][LF]
00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_01_00_00_[CR][LF]
00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_32_00_00_00_00_[CR][LF]
00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_[CR][LF]
00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_[CR][LF]
00_00_00_00_00_00_00_CC_[CR][LF]
If you requested discrete bit information, the returned data will contain
two counters and the discrete bit results. Each counter has 12 positions
(10 characters, 2 spaces) reserved for a maximum value of 4,294,967,295.
Note: Counters are decimal values. All other fields are hexadecimal values.
The counter data is left justified and the remaining field is filled with
spaces. The first counter contains the total number of triggers processed.
The second counter contains the total number of faults. Both counters are
expressed as decimal values. The results bit information (128 bits), which
follows the counters, is 16 bytes long. Each byte is represented by two
hexadecimal characters (00 through FF) followed by a space. The
following is an example of the returned data format:
Discrete Bit Results Returned Data Format
[CR][LF]
1234567890__1234567890__80_00_00_00_00_00_00_00_00_00_00_00_00_00_00_00_[CR][LF]
Refer to Appendix B for a description of the returned bytes.
Use the Save command to transfer CVIM module configuration data to the
local storage area (EEPROM) or the external RAM card (credit card
memory).
Note: Depending upon the card size, up to 16 configurations can be saved to
the RAM card (512K card).
Use one of the following commands:
>S[CR]
Transfers configuration data from the
CVIM module RAM to the EEPROM.
>S,CC,X [CR]
Transfers configuration data from the
CVIM module RAM to the RAM card
area X (01 –16).
Read Inspection Results
(cont’d)
Save Configuration