beautypg.com

Obtaining inspection result information, Cvim module configuration instructions – Rockwell Automation 5370 CVIM Communications Manual User Manual

Page 44

background image

Chapter 4
Using the Remote I/O Link
(Node Adapter)

4–7

You can obtain inspection result information for each of the inspection tools
over the Remote I/O link. There are two levels of access to this information:

Discrete Bits. These bits indicate pass/fail/warning data.

Result Data Words. These words contain actual inspection result data such
as measured lengths, number of black pixels, etc.

Note: Refer to Appendix B for a description of the discrete bit results and
Appendix C for a description of numerical results data blocks.

If you are using the Remote I/O link to communicate with a PLC–2, –3, or
–5 (or PLC–5/250 in another rack), you must configure the CVIM module as
follows:

Select the Remote I/O port for communications:

Note: This step is not required if you are only reading results.

4. Select the setup menu .

5. Select the environment menu .

6. Select the system menu .

7. Select a Host menu or .

8. Select remote I/O option .

Note: Unless a separate configuration host is being used, set both the CFG
Host & SYS Host for Remote I/O.

Configure CVIM module I/O parameters:

9. Select the I/O menu .

10.Select <1771 Remote I/O> option.

11. Enable the Remote I/O port by selecting .

12.Select the rack address (octal) using the keypad.

13.Select the baud rate <57.6Kbaud> or other options.

Select the CVIM module trigger source:

14.Select the trigger source menu .

15.Select the trigger source menu for the appropriate toolset

Source>.

16.Select either , , or trigger sources.

Note: The example connection diagram shown on Figure 4.9 shows a trigger
using the local I/O board.

Obtaining Inspection
Result Information

CVIM Module
Configuration Instructions