Accessing discrete bit information (cont’d) – Rockwell Automation 5370 CVIM Communications Manual User Manual
Page 46

Chapter 4
Using the Remote I/O Link
(Node Adapter)
4–9
Table 4.A
CVIM Module Remote I/O Inputs (CVIM Module to PLC) if CVIM Module is Rack 02
BIT
07
–––
17
06
–––
16
05
–––
15
04
–––
14
03
–––
13
02
–––
12
01
–––
11
00
–––
10
W
O
R
D
(Not used)
1=Data Valid
0=First Bits
Results
1 = Trigger
Missed
1 = Module
Busy
1 = PLC is
Master
1 = Config.
Error
(Not Used)
1 = Master
Fault
1 = Light
Probe Failed
1 = Reference
Window 3
Failed
1 = Reference
Window 2
Failed
1 = Reference
Window 1
Failed
1 = Reference
Line 3 Failed
1 = Reference
Line 2 Failed
1 = Reference
Line 1 Failed
20
1 = Window 4
Fault
1 = Window 4
Warning
1 = Window 3
Fault
1 = Window 3
Warning
1 = Window 2
Fault
1 = Window 2
Warning
1 = Window 1
Fault
1 = Window 1
Warning
21
1 = Window 8
Fault
1 = Window 8
Warning
1 = Window 7
Fault
1 = Window 7
Warning
1 = Window 6
Fault
1 = Window 6
Warning
1 = Window 5
Fault
1 = Window 5
Warning
21
1 = Window
12 Fault
1 = Window
12 Warning
1 = Window
11 Fault
1 = Window
11 Warning
1 = Window
10 Fault
1 = Window
10 Warning
1 = Window 9
Fault
1 = Window 9
Warning
22
1 = Window
16 Fault
1 = Window
16 Warning
1 = Window
15 Fault
1 = Window
15 Warning
1 = Warning
14 Fault
1 = Window
14 Warning
1 = Window
13 Fault
1 = Window
13 Warning
22
1 = Window
20 Fault
1 = Window
20 Warning
1 = Window
19 Fault
1 = Window
19 Warning
1 = Window
18 Fault
1 = Window
18 Warning
1 = Window
17 Fault
1 = Window
17 Warning
23
1 = Window
24 Fault
1 = Window
24 Warning
1 = Window
23 Fault
1 = Window
23 Warning
1 = Window
22 Fault
1 = Window
22 Warning
1 = Window
21 Fault
1 = Window
21 Warning
23
1 = Gage 4
Fault
1 = Gage 4
Warning
1 = Gage 3
Fault
1 = Gage 3
Warning
1 = Gage 2
Fault
1 = Gage 2
Warning
1 = Gage 1
Fault
1 = Gage 1
Warning
24
1 = Gage 8
Fault
1 = Gage 8
Warning
1 = Gage 7
Fault
1 = Gage 7
Warning
1 = Gage 6
Fault
1 = Gage 6
Warning
1 = Gage 5
Fault
1 = Gage 5
Warning
24
1 = Gage 12
Fault
1 = Gage 12
Warning
1 = Gage 11
Fault
1 = Gage 11
Warning
1 = Gage 10
Fault
1 = Gage 10
Warning
1 = Gage 9
Fault
1 = Gage 9
Warning
25
1 = Gage 16
Fault
1 = Gage 16
Warning
1 = Gage 15
Fault
1 = Gage 15
Warning
1 = Gage 14
Fault
1 = Gage 14
Warning
1 = Gage 13
Fault
1 = Gage 13
Warning
25
1 = Gage 20
Fault
1 = Gage 20
Warning
1 = Gage 19
Fault
1 = Gage 19
Warning
1 = Gage 18
Fault
1 = Gage 18
Warning
1 = Gage 17
Fault
1 = Gage 17
Warning
26
1 = Gage 24
Fault
1 = Gage 24
Warning
1 = Gage 23
Fault
1 = Gage 23
Warning
1 = Gage 22
Fault
1 = Gage 22
Warning
1 = Gage 21
Fault
1 = Gage 21
Warning
26
1 = Gage 28
Fault
1 = Gage 28
Warning
1 = Gage 27
Fault
1 = Gage 27
Warning
1 = Gage 26
Fault
1 = Gage 26
Warning
1 = Gage 25
Fault
1 = Gage 25
Warning
27
1 = Gage 32
Fault
1 = Gage 32
Warning
1 = Gage 31
Fault
1 = Gage 31
Warning
1 = Gage 30
Fault
1 = Gage 30
Warning
1 = Gage 29
Fault
1 = Gage 29
Warning
27
Accessing Discrete
Bit Information (cont’d)