Chapter 5

Using the RS-232 Ports

5–43

15 (hex) = Resume – Toolset 2
16 (hex) = Reset Statistics – Toolset 2
17 (hex) = Reset counters – Toolset 2
18 (hex) = Page up – Toolset 2
19 (hex) = Page down – Toolset 2

Examples:

03

This example displays all tools in toolset 1.

01

This example selects go on reject in toolset 1.

0B

14

05

Operation

Object

Data

This example selects page down in toolset 2.

If the BCC is not valid, the CVIM module will respond with a DLE NAK
and the command will not be executed.

If the BCC is valid, the CVIM module will respond with a DLE ACK. Then
the CVIM module will validate the command structure. If the command is
valid, the CVIM module will execute the command and return the data. If the
command structure is invalid, the CVIM module will not execute the
command or respond.