Appendix a - worksheets, Blank worksheets – Rockwell Automation 1771-QDC, D17716.5.87(Passport) CLAMP AND EJECT MODE User Manual
Page 201

Select System Operation with bits 05 and 04
Clamp and Eject 1 0
Select SingleĆunit Operation with bit 03 = 1
(0 generates a programming error)
Select English = 0 or
metric = 1 with bit 00
Code:
Your value
Required initial value
loaded by ProĆSet 600
0 or 1
Input Range
0 - 10V dc
0
0
1 - 5V dc
0
1
4 - 20 mA
1
0
Not connected
1
1
Select Input 1 (Ejector Position) Range with bits 01, 00
Select Input 2 (Ejector Pressure) Range with bits 03, 02
Select Input 3 (Clamp Position) Range with bits 05, 04
Select Input 4 (Clamp Pressure) Range with bits 07, 06
Code:
Your value
Required initial value
loaded by ProĆSet 600
0 or 1
Appendix
A
A-1
Blank Worksheets
Worksheet 3ĆA
Selecting Module Parameters
Control Word MCC02ĆBxx
15
14 13 12
11
10
09 08 07 06 05 04 03 02 01 00
ProĆSet 600 Addr. B35/bit
543 542 541 540 539 538 537 536 535 534 533 532 531 530 529 528
Value
0
0
0
0
0
0
0
0
0
0
0
0
Example: If you select Clamp and Eject operation with English units:
MCC02 = 00000000 00101000
Worksheet 3ĆB
Selecting Input Ranges for your Sensors
Control Word MCC03ĆBxx
15
14 13 12 11
10
09 08 07 06 05 04 03 02 01 00
ProĆSet 600 Addr. B34/bit
559 558 557 556 555 554 553 552 551 550 549 548 547 546 545 544
Value
1
1
1
1
1
1
1
1
Example: If you select an input range of 4-20mA for all four inputs,
MCC03 = 11111111 10101010.