Compactlogix example using generic profile – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 99
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
99
Using Multi-Drive Mode
Chapter 7
Drive 1...4 (PowerFlex 4M) Settings for the Example Program
The following parameters are set:
CompactLogix Example Using
Generic Profile
The following common Tags are used:
The following Tags are used for Drive 0:
The same type of Tags are also used for Drive 1 through Drive 4.
Value
Parameter
Drive 1
Drive 2
Drive 3
Drive 4
P106 [Start Source]
5
5
5
5
P108 [Speed Reference]
5
5
5
5
C302 [Comm Data Rate]
4
4
4
4
C303 [Comm Node Addr]
1
2
3
4
C304 [Comm Loss Action]
0
0
0
0
C305 [Comm Loss Time]
5.0 s
5.0 s
5.0 s
5.0 s
C306 [Comm Format]
0
0
0
0
Tag Name
Type
Description
PowerFlex_52X_Drive_Multi_Generic:O
AB:ETHERNET_MODULE_xxx:O:0
Generic EtherNet/IP
module I/O tags and
configuration
PowerFlex_52X_Drive_Multi_Generic:I
AB:ETHERNET_MODULE_xxx:I:0
PowerFlex_52X_Drive_Multi_Generic:C
AB:ETHERNET_MODULE:C:0
Accel_Time_1
INT
–
Drive_Input_Image
INT [12]
Input Image Table
Drive_Output_Image
INT [10]
Output Image Table
Tag Name
Type
Description
Drive_0_Command_Stop
BOOL
Logic Command bit 0 (STOP)
Drive_0_Command_Start
BOOL
Logic Command bit 1 (START)
Drive_0_Command_Jog
BOOL
Logic Command bit 2 (JOG)
Drive_0_Command_Clear_Faults
BOOL
Logic Command bit 3 (CLEAR FAULTS)
Drive_0_Command_Forward
BOOL
Logic Command bit 4 (FORWARD)
Drive_0_Reference
INT
Speed Reference
Drive_0_Status_Ready
BOOL
Logic Status bit 0 (READY)
Drive_0_Status_Active
BOOL
Logic Status bit 1 (ACTIVE)
Drive_0_Status_Forward
BOOL
Logic Status bit 2 (FORWARD)
Drive_0_Status_Faulted
BOOL
Logic Status bit 7 (FAULT)
Drive_0_Status_At_Reference
BOOL
Logic Status bit 8 (AT SPEED)
Drive_0_Feedback
INT
Speed Feedback
Perform_Parameter_Read_0
BOOL
Initiates the parameter read
Parameter_RD_Value_0
INT
Read value of the parameter
Parameter_RD_Message_0
MESSAGE
Get_Attribute_Single (Read)
Perform_Parameter_Write_0
BOOL
Initiates the parameter value
Parameter_WR_Value_0
INT
Write value to the parameter
Parameter_WR_Message_0
MESSAGE
Set_Attritbute_Single (Write)