Configuring the rs-485 network – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 86
86
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Chapter 7
Using Multi-Drive Mode
Multi-Drive Example of I/O Image
(1) Padwords only apply when using the generic profile. Padwords are not used when using the full-featured drive Add-On-Profile.
Note:
If a daisy-chained drive is disconnected from the RS-485 (DSI) network
or powered down, the Logic Status and Feedback words for the affected drive will
be set to 0.
Configuring the RS-485
Network
The following parameters must be set in the daisy-chained PowerFlex 4M drives
and not in the master drive:
Note:
The RS-485 Multi-drive network is fixed at 19.2K baud rate, 8 data bits,
no parity, and 1 stop bit.
Controller
Scanner
Adapter
Word and I/O
EtherNet/IP
DSI
Output
Image
(Write)
Input
Image
(Read)
Message
Handler
Message
Buffer
Logic Command
Word 0
Reference
Word 1
Drive 0
Logic Command
Word 2
Reference
Word 3
Logic Command
Word 4
Reference
Word 5
Logic Command
Word 6
Reference
Word 7
Logic Command
Word 8
Reference
Word 9
PowerFlex Drive 2
PowerFlex Drive 0
PowerFlex Drive 1
PowerFlex Drive 3
PowerFlex Drive 4
PowerFlex Drive 0
PowerFlex Drive 1
PowerFlex Drive 2
PowerFlex Drive 3
PowerFlex Drive 4
Drive 1
Drive 2
Drive 3
Drive 4
Logic Status
Word 2
Feedback
Word 3
Drive 0
Padword
(1)
Word 0
Padword
Word 1
Logic Status
Word 4
Feedback
Word 5
Logic Status
Word 6
Feedback
Word 7
Logic Status
Word 8
Feedback
Word 9
Logic Status
Word 10
Feedback
Word 11
Drive 1
Drive 2
Drive 3
Drive 4
Parameter
Value
P106 [Start Source]
5 “Comm Port”
P108 [Speed Reference]
5 “Comm Port”
C302 [Comm Data Rate]
4 “19.2K”
C303 [Comm Node Addr]
1...247 (must be unique)
C306 [Comm Format]
0 “RTU-8-N-1”