beautypg.com

Class attributes, Instance attributes, Class attributes instance attributes – Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual

Page 133

background image

Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013

133

EtherNet/IP Objects

Appendix C

In addition, the parameters for the other DSI devices can be accessed using the
instance-offset encoding shown in the table below:

Class Attributes

Instance Attributes

Instances (Hex.)

Instances (Dec.)

Single-Drive Mode

Multi-Drive Mode

0x0000...0x3FFF

0...16383

Instances 0...1023 in the drive

Instances 0...1023 in Drive 0

0x4000...0x43FF

16384...17407

Instances 0...1023 in the interface

(1)

(1) Interface is the current interface being used to access the information. Note: If using the embedded EtherNet/IP adapter, this

instance range contains the same data as Drive 0.

Instances 0...1023 in the interface

(1)

0x4400...0x47FF

17408...18431

DSI

Instances 0...1023 in Drive 1

0x4800...0x4BFF

18432...19455

Option

Instances 0...1023 in Drive 2

0x4C00...0x4FFF

19456...20479

Not supported

Instances 0...1023 in Drive 3

0x5000...0x53FF

20480...21503

Not supported

Instances 0...1023 in Drive 4

0x5400...0x57FF

21504...22527

Not supported

Instances 0...1023 in the Option

Attribute ID

Access Rule

Name

Data Type

Description

1

Get

Revision

UINT

1

2

Get

Max Instance

UINT

Number of parameters

8

Get

Parameter Class Descriptor

WORD

0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS

9

Get

Configuration Assembly Instance

UINT

0

10

Get

Native Language

USINT

1 = English
2 = French
3 = Spanish
4 = Italian
5 = German
6 = Japanese
7 = Portuguese
8 = Chinese Simplified
9 = Reserved
10 = Reserved
11 = Korean
12 = Polish
13 = Reserved
14 = Turkish
15 = Czech

Attribute ID

Access Rule

Name

Data Type

Description

1

(1)

Parameter Value

(2)

(3)

2

Get

Link Path Size

USINT

0 = No link specified
n = The size of Attribute 3 in bytes

3

Get

Link Path

(4)

4

Get

Descriptor

WORD

0 = False, 1 = True
Bit 1 = Supports ENUMs
Bit 2 = Supports scaling
Bit 3 = Supports scaling links
Bit 4 = Read only
Bit 5 = Monitor
Bit 6 = Extended precision scaling