Rockwell Automation 25B PowerFlex 525 Embedded EtherNet/IP Adapter User Manual
Page 120
120
Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013
Appendix B
Adapter Parameters
C127
[RS485 Format]
Determines the details related to the specific Modbus protocol
used by the drive. A reset or power cycle is required after
selection is made.
Default:
0 = RTU 8-N-1
Values:
0 = RTU 8-N-1
1 = RTU 8-E-1
2 = RTU 8-O-1
3 = RTU 8-N-2
4 = RTU 8-E-2
5 = RTU 8-0-2
Type:
Read/Write
Reset Required:
Yes
C128
[EN Addr Sel]
Enables BOOTP to set the IP address, subnet mask and gateway
address with a BOOTP server. Identifies the connections that
would be attempted on a reset or power cycle. A reset or power
cycle is required after selection is made.
Default:
2 = BOOTP
Values:
1 = Parameters
2 = BOOTP
Type:
Read/Write
Reset Required:
Yes
C129
C130
C131
C132
[EN IP Addr Cfg 1]
[EN IP Addr Cfg 2]
[EN IP Addr Cfg 3]
[EN IP Addr Cfg 4]
Sets the bytes in the IP address. A reset or power cycle is
required after selection is made.
Important: To set the IP address using these parameters, C128
[EN Addr Sel] must be set to 1 “Parameters”.
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
C133
C134
C135
C136
[EN Subnet Cfg 1]
[EN Subnet Cfg 2]
[EN Subnet Cfg 3]
[EN Subnet Cfg 4]
Sets the bytes of the subnet mask. A reset or power cycle is
required after selection is made.
Important: To set the subnet mask using these parameters,
C128 [EN Addr Sel] must be set to 1 “Parameters”.
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required:
Yes
Parameter
No.
Name and Description
Details
192.168.1.62
[EN IP Addr Cfg 1]
[EN IP Addr Cfg 2]
[EN IP Addr Cfg 3]
[EN IP Addr Cfg 4]
255.255.255.0
[EN Subnet Cfg 1]
[EN Subnet Cfg 2]
[EN Subnet Cfg 3]
[EN Subnet Cfg 4]