Rockwell Automation Publication 520COM-UM001B-EN-E - March 2013

Chapter 7

Using Multi-Drive Mode

Correlating the Drive with the Controller

You must now correlate the drive settings to the RSLogix 5000/Logix Designer
project I/O settings so that they match. This requires loading the project I/O
settings into the drive.

1.

In the treeview under I/O Configuration, right-click on the drive profile
(for this example “PowerFlex 525-EENET PowerFlex_52X_Drive”) and
select Properties.

2.

Select the Drive tab to begin the correlation process.

After the drive configuration data has been verified, the Drive tab will
display a request to synchronize the configuration with the drive. Click
Upload

. The correlation process will continue. This may take several

minutes depending on the number and type of daisy-chained drives.

If the

Differences Found Screen on page 97

appears—which is typical,

click Download. This will download the project settings from the
controller to the drives. If Upload is clicked, the drive settings are
uploaded to the controller.

TIP

On subsequent connections to the drive (after the initial download),
select Upload.