CANopen

6

Parameter setting

6-31

L

BA2175 EN 2.0

6.4.1.4

1005

hex

: Identifier sync message

This object ensures that

sync telegrams can be created for a module.

the identifier value can be written.

Index [hex] Subindex

Name

Data type

Authorisation

1005

0

Identifier sync message

U32

rw

Sync telegram creation

Sync telegrams are created when bit 30 (see below) is set to 1.

The time between to sync telegrams can be set using a different object (index 1006

hex,

see chapter

6.4.1.5).

Identifier writing

The default setting for receiving PDOs is 80

hex

in bit 11 (also according to CANopen). This means

that all modules are default set to the same sync telegram.
If sync telegrams are only to be received by certain modules, their identifiers can be entered with
values up to 7FF

hex

.

5th byte

6th byte

7th byte

8th byte

U32

0

10

11 - 28

29

30

31

11 bit identifier

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0/1

X

Bit no.

Value

Explanation

0 - 10

X

Identifier (see chapter 6.1.1)

(11 - 28)*

0

*

)

The extended identifier (29 bit) is not supported for the 2175 fieldbus Any of these bits must be 0

29*

0

*

)

The extended identifier (29 bit) is not supported for the 2175 fieldbus. Any of these bits must be 0.

30

0
1

Device does not create SYNC telegrams
Device creates SYNC telegrams

31

X

Any

6.4.1.5

1006

hex

: Communication cycle period

Setting of sync telegram cycle time

Index [hex] Subindex

Name

Data type

Authorisation

1006

0

Communication cycle period

U32

rw

With the default setting of t = 0, sync telegrams are not created.

Cycle times can be entered as 1000 or an integer multiple of 1000. The unit of the entered time
is [

µ

s].

6.4.1.6

1008

hex

: Manufacturer’s device name

Controller and module name and code

Index [hex] Subindex

Name

Data type

Authorisation

1008

0

Manufacturer device name

Visible string
{9 characters}

const