beautypg.com

Devicenet – Lenze EMF2175IB User Manual

Page 117

background image

DeviceNet

12

Parameter setting

12-7

L

BA2175 EN 2.0

12.2

Notes to be observed for paramater setting

12.2.1

8200 controllers

The following applies to the 8200 inverter series:

Caution!

Parameter setting (codes except C046, C0135) is only possible when the controller is inhibited.
Parameters are accepted when the controller is enabled, but they are not saved.
After having set a parameter, the controller must not be addressed for approx. 50 ms; otherwise the
command will be ignored.

After parameter setting, the controller needs up to approx. 70 ms to set the status ’enabled’
(terminal, C040, C0135).

The TRIP reset function is activated by inhibiting the controller and enabling it again under C040 or
C0135.

The TRIP reset function initializes the 8200 inverter and the 2175 fieldbus module. Therefore the
TRIP reset command is not acknowledged for the master.

12.2.2

8200 vector controllers

Digital and analog input and output signals can be freely configured (see Operating Instructions;
codes C0410, C0412, C0417 and C0421)

Show/Hide Bookmarks