DeviceNet

10

Installation

10-3

L

BA2175 EN 2.0

10.3

Electrical installation

10.3.1

Selection of the transmission cable

The devices are connected to the bus by means of a fieldbus cable which must comply with the
DeviceNet

Ô

specification (release 2.0). Companies like Belden Wire & Cable, Olflex Wire & Cable,

C&M Corp. and Madison Cable manufacture DeviceNet

Ô

“ thick” - and “ thin” cables.

Stop!

If you do not want to use “ thick” or “ thin” cables, the cables used must comply with the requirements
of the DeviceNet Specification (see chapter 10.410.5).
Any other cable is not permitted and must not be used.

10.3.2

Assignment of the plug/ socket connector

The 2175 fieldbus module is connected to the bus through a 5 pole plug/socket connector.

The assignment of the plug/socket connector and the cable colour used according to the DeviceNet
Specification is listed in the table.

5

4

3

2

1

2175

Thick

Thin

120R

Terminal

Designation

Cable colour

Explanation

1

V-

black

GND; reference for external voltage supply

2

CAN_L

blue

Data cable / input for terminating resistance of 120 Ohm

3

SHIELD

Shield

4

CAN_H

white

Data cable / input for terminating resistance of 120 Ohm

5

V+

red

External voltage supply; see notes in chapter 10.3.3

2175DeN007

+V

cc

+V

cc

+V

CAN+

Shield

CAN-

- V

7

6

2

8

5

3

1

4

DC

DC

Tab. 10-1

Terminal assignment