DeviceNet Modules

HE800DNM650 & HE800DNS600

Variable Meaning

Received message

number of received CAN-Messages

Sent messages

number of sent CAN-Messages

Receive overruns

this counter is incrementing when to many incoming CAN
messages overload the Master. An incremented counter will
always cause lost CAN message data, so it should normally
contain the value 0

Received Overruns

our DeviceNet controller has two internal error frame counter
for detected

Low Transmission Quality if the internal DeviceNet controller error frame counter

overstep a defined limit

Bus Off Counter

This number will increment when the bus is off or not powered
during bus cycles

Baudrate

this value shows numeric the actual baudrate the Master is
working with (, 1 = 500kBaud, 2 = 250Kbaud, 3 = 125kBaud)

Activated bus parameters value 0, the Master has found a configuration data base

coming from HSyCon, value 1, the Master device isn’t
configured and need to be configured via HSyCon

Announced Nodes

this value represents the number of found device data sets in
the download database

Wrong parameters

this value indicates, if the Master has detected errors in a
device data set which was a containment of the actual
downloaded database. For each Slave device that has a
wrong entry the counter is incremented by 1

Hard Transmission Aborts this value indicates transmission aborts by the Master

Table 44: DNM_TASK Common Variables