beautypg.com

Horner APG SmartStack I/O HE800DNS600/HEDNS600 User Manual

Page 62

background image

MAN0577-03-en

Page 62 of 98

EO 09-0009

DeviceNet Modules

HE800DNM650 & HE800DNS600





It is recommend to create a sub-directory MSG and to store the messages in it.

Figure 40: Save a Message

6.28. Message Monitor for testing explicit messaging of DeviceNet

In the following, the Message Monitor for reading and writing data via DeviceNet at the Master is
described.
The following must be entered in the Message Monitor in order to read or write data via DeviceNet from a
Device:

Message header

Rx = 3 (always)

Tx = 255

Ln = (calculated)

Nr = 0 .. 255

A = 0

F = 0

B = 17

E = 0

Telegram header

Meaning for DeviceNet

Value range

Device Adr

MAC ID of the device

0 .. 63

Data Area

Class ID

0 .. 32

Data Address

Instance ID

0 .. 255

Data Index

Attribute ID

0 .. 255

Data Count

Data Count
Unused in read access
length of attribute data in
write access


0
1 – 240

Data Type

Data Type, unused

0

Function

Read
Write

1
2

Table 19: Message Monitor – Example DeviceNet