Horner APG SmartStack I/O HE800DNS600/HEDNS600 User Manual
Page 62

MAN0577-03-en
Page 62 of 98
EO 09-0009
DeviceNet Modules
HE800DNM650 & HE800DNS600
It is recommend to create a sub-directory MSG and to store the messages in it.
Figure 40: Save a Message
6.28. Message Monitor for testing explicit messaging of DeviceNet
In the following, the Message Monitor for reading and writing data via DeviceNet at the Master is
described.
The following must be entered in the Message Monitor in order to read or write data via DeviceNet from a
Device:
Message header
Rx = 3 (always)
Tx = 255
Ln = (calculated)
Nr = 0 .. 255
A = 0
F = 0
B = 17
E = 0
Telegram header
Meaning for DeviceNet
Value range
Device Adr
MAC ID of the device
0 .. 63
Data Area
Class ID
0 .. 32
Data Address
Instance ID
0 .. 255
Data Index
Attribute ID
0 .. 255
Data Count
Data Count
Unused in read access
length of attribute data in
write access
0
1 – 240
Data Type
Data Type, unused
0
Function
Read
Write
1
2
Table 19: Message Monitor – Example DeviceNet