Horner APG SmartStack I/O HE800DNS600/HEDNS600 User Manual
Page 65
MAN0577-03-en
Page 65 of 98
EO 09-0009
DeviceNet Modules
HE800DNM650 & HE800DNS600
7.3.2.1. DataType Code
D7 D6 D5 D4 D3 D2 D1 D0
SubFlag Data Direction
Data Format
according EN standard
0 blank space
1 Boolean
2 Integer 8
3 Integer 16
4 Integer 32
5 Unsigned Integer 8
6 Unsigned Integer 16
7 Unsigned Integer 32
8 Float
9 ASCII
10 String
14 Bit
0 emty space
1 input
2 output
0 start of a module
1 submodule
Table 21: CSV Export > DataType Code
7.3.2.2. DataPosition Code
D7 D6 D5 D4 D3 D2 D1 D0
Reserved Area
Bit Position
Bit Position of the Offset Address
reserved
Table 22: CSV Export - DataPosition Code
Example of a CSV file which was exported in Excel:
Table 23: Example of a CSV file in Excel format
The DeviceNet Salve device has the Station address 1 (A1).
The RecordType is default 2 (B1).
The IdentNumber of the Slave is 0 (C1).
No VendorNumber is available, so this is 0 (D1).
The VendorName is empty (Horner) (E1).
The Device has the description OCS200_DeviceNet (F1).
The Description of the Device is HE500OCS200DNet (G1).
The Masteraddress is 255 (H1).
There are Settings of the I/O data, so this is 3, (I1).
This field is Reserved, because of "reserved" is displayed (J1).
The number of the actual modules is 2, so in the field ModulCount a 2 is shown (K1).
The DataType of module 1 is 2 (K1).
The DataSize of the first module is 32 (L1).