Horner APG SmartStack I/O HE800DNS600/HEDNS600 User Manual
Page 21

MAN0577-03-en
Page 21 of 98
EO 09-0009
DeviceNet Modules
HE800DNM650 & HE800DNS600
3.5
Configuring a Horner DeviceNet Master with a Horner DeviceNet Slave
Table 6 below describes the steps to configure a SmartStack DeviceNet Master to a Smartstack
DeviceNet slave :
Action
Menu in the System Configurator
•
Create a new project
File > New > DeviceNet
•
Choose Horner DeviceNet Master and provide MAC ID address
Insert > Master
•
Choose Horner DeviceNet Device (Slave) and provide MAC ID
address
Insert > Device
•
Assign the input and output modules
Mark the Device (left Mouse click), then
Settings > Device Configuration
•
Assign the offset addresses (*1)
•
Set the Bus parameter
Mark the Master (left Mouse click), then
Settings > Bus Parameters
•
Set device assignment for the Master if no automatic assignment
has occurred
Mark the Master (left Mouse click), then
Settings > Device Assignment
•
Set device assignment for the Device (Slave) if no automatic
assignment has occurred
Mark the Device (left Mouse click), then
Settings > Device Assignment
•
Save project
File > Save
•
Download to the Master
Mark the Master (left Mouse click), then
Online > Download
•
Download to the Device (Slave)
Mark the Device (left Mouse click), then
Online > Download
•
Live list
Mark the Master (left Mouse click), then
Online > Live List
•
Start Debugger
Mark the Master (left Mouse click), then
Online > Start Debug Mode
•
Device diagnostic
Mark the Device (left Mouse click), then
Online > Device Diagnostic
•
Stop Debugger
Online > Stop Debug Mode
•
Global Diagnostic
Mark the Master (left Mouse click), then
Online > Global State Field
•
Transfer user data:
Write output, read input
Mark the Master (left Mouse click), then
Online > I/O Monitor
Table 6: Steps to configure a DNM650 with DNS600’s.
Note (*1): The Offset addresses assigned in the Slave configuration are always related to the DeviceNet
Master.