DeviceNet Modules

HE800DNM650 & HE800DNS600

Example:

Figure 25: Online > Automatic Network Scan (after scan)

In our example in the figure above the automatic network scan detected a Horner device at MAC ID 1.
Here is an explanation of the different columns:

Variable Meaning

Supported functions

Functions supported by the device, could be polled, bit strobe
or cyclic/change of state (see explanation in Actual chosen IO
Connection page 27)

Device Name

Name of the device, result from network scan

Poll Size Produced

Number of data for poll connection (input)

Poll Size Consumed

Number of data for poll connection (output)

BitStr. Size Produced

Number of data for bit strobe connection (input)

BitStr. Size Consumed

Number of data for bit strobe connection (output)

Cyc/COS. Size Produced Number of data for cyclic/COS connection (input)
Cyc/COS. Size Consumed Number of data for cyclic/COS connection (output)

Chosen Config

Configuration chosen by the user, could be Change of State,
Cyclic, Polling, Bit strobed or explicit only and depends on the
functions supported by the device. Click on the cell to change
the configuration.

Table 10: Meaning of the columns in the automatic network scan

A double click on the first or second column of the corresponding row of the device shows information of
the device