Horner APG SmartStack I/O HE800DNS600/HEDNS600 User Manual
Page 75

MAN0577-03-en
Page 75 of 98
EO 09-0009
DeviceNet Modules
HE800DNM650 & HE800DNS600
8.3. RCS Error Numbers (4 .. 93)
This is the list of error numbers returned by the RCS (Realtime Communication System), that is the
operating system of Horner devices. The error number is returned in an answer message. Command
messages and answer messages are used to communicate between the application (e.g. the System
Configurator) and the Horner device. An example of this communication is the download of a
configuration.
Error Number Description
4
Task does not exist
5
Task is not initialised
6
The MCL is locked
7
The MCL rejects a send command because of an error
20
The user will download a database into the device that is not valid for
this device type.
21
Data base segment not configured or not existed
22
Number for message wrong during download
23
Received number of data during download does not match to that in the
command message
24
Sequence identifier wrong during download
25
Checksum after download and checksum in command message do not
match
26
Write/Read access of data base segment
27
Download/Upload or erase of configured data base type is not allowed
28
The state of the data base segment indicated an error. Upload not
possible
29
The access to the data base segment needs the bootstraploader. The
bootstraploader is not present
30
Trace buffer overflow
31
Entry into trace buffer too long
37
No or wrong licence. The OEM licence of the System Configurator
allows only communication to devices that have the same licence inside
38
The data base created by the System Configurator and the data base
expected by the firmware is not compatible
39
DBM module missing
Table 31: RCS error numbers (answer message) (4..39)