Red Lion IndustrialPr 6000 Router User Manual
Page 138
Software User Guide
138
Automation Tab
Object 31 ‐ Frozen Analog Input: This field is activate by both Levels 2 and 2+. It’s used to determine if a DNP point will
generates events (Object2 Binary Change Events) then it should be associated to a class (Class 1, Class 2 or Class 3),
otherwise it should be associated to None. By default all DNP Points don’t generate events, this feature should be
modified by the user.
Object 32 ‐ Analog Change Event: This field is activate by both Levels 2 and 2+. It’s used to determine if a DNP point
will generates events (Object2 Binary Change Events) then it should be associated to a class (Class 1, Class 2 or Class
3), otherwise it should be associated to None. By default all DNP Points don’t generate events, this feature should be
modified by the user.
Object 33 ‐ Frozen Change Event: This field is activate by both Levels 2 and 2+. It’s used to determine if a DNP point
will generates events (Object2 Binary Change Events) then it should be associated to a class (Class 1, Class 2 or Class
3), otherwise it should be associated to None. By default all DNP Points don’t generate events, this feature should be
modified by the user.
•
Click Finish to enter your exception into the table.
•
To edit an entry, select the station in the table and click on the edit button. To delete an existing entry, select the
station in the table and click on the Delete button.
•
Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map‐
ping button to return to the DNP3 Object Mapping Configuration dialog window.
Floating Outputs Map I/O:
Configure DNP Points: If No is selected, then no Analog Outputs are mapped as DNP points. If set to Yes, the Highest
Register Address field is activated.
Highest Register Address (Required): This field is used to show or set the highest register address to map DNP points.
•
Click on Store I/O Mapping to save your configuration before moving to the next project. Click on the Object Map‐
ping button to return to the DNP3 Object Mapping Configuration dialog window.
Long Inputs Map I/O: This option provides configuration of Mapping Long Input I/O’s Reg/Index to DNP points
for generating events based on configured DeadBand and Class Assignments when the status of any Long Input
I/O’s changes.
Default DeadBand and Class Assignments are applied to all the Reg/Index defined by Highest Register Address except Reg/
Index entries that are defined in Exception DeadBand and Class Assignments Table.