Table 2 ‐ I/O Types and Limits for write commands
I/O Type
Number of regs supported in I/O transfer
Discrete Input
DI
1968
Discrete Output
DO
1968
Analog Input
AI
123
Analog Output
AO
123
Float Input
FI
61
Float Output
FO
61
Long Input
LI
61
Long Output
LO
61
Table 3 ‐ Valid Type Combinations for READ I/O Xfers
Local Type
Valid Remote Type
DI
DI | DO
DO
DI | DO
AI
AI | AO
AO
AI | AO
FI
FI | FO
FO
FI | FO
LI
LI | LO
LO
LI | LO
Table 4 ‐ Valid Type Combinations for WRITE I/O Xfers
Local Type
Valid Remote Type
DI
DO
DO
DO
AI
AO
AO
AO
FI
FO
FI
FO
LI
LO
LO
LO