2cdaqmx::setmxconfig, Cdaqmx::setoutput – Yokogawa PC-Based MX100 User Manual
Page 88

2-65
IM MX190-01E
MX100 -Visual C++
2
CDAQMX::setMXConfig
Syntax
int setMXConfig(CDAQMXConfig & cMXConfig);
Parameters
cMXConfig
Specify the setup data.
Description
Sets basic settings on the device.
The input data is validated before it is sent.
The FIFO stops. If auto control is enabled, the FIFO starts after the function
completes successfully.
Packets differ with the style number of the main unit.
The setting item number of the validation results are stored in the setting item
number field of the data member.
Return value
Returns an error number.
Error:
Not data
The input data is not valid.
Not support
Unsupported version.
Reference
getNo getPacketVersion getUserTime runCommand startFIFO
stopFIFO CDAQMXConfig::isCorrect CDAQMXConfig::getItemError
CDAQMX::setOutput
Syntax
int setOutput(CDAQMXOutputData & cMXOutputData);
Parameters
cMXOutputData Specify the output channel data.
Description
Sets the output channel data.
Gets the setup data, updates it according to the specified output channel data, and
sends the setup data.
If the output type is changed, it will not match the channel setup data.
Return value
Returns an error number.
Reference
getMXConfig setMXConfig CDAQMXConfig::getClassMXOutputData
2.5 Details of the MX100 Class