beautypg.com

E-Mon Energy Software User Manual

Page 141

background image

Access Location

E-Mon Energy User Manual

14-4

E-MON

Flag Status Button

The Flag Status provides an alert in the E-Mon Energy™ software of a problem or power failure. The two

failures illustrated below indicate the date and time of the last failure. The Power Failure Status indicates that

the IDR has lost power at some point. To reset (clear) the flags, click on the Clear Flag button. For complete

instructions, see Error Flag section within this manual.

Figure 14.8 - Access Location Function – Flag Status

Columns

Description

Status

This column displays the condition of the device. If the condition

states “Bad” or “Timeout,” there is a possible error in reading the

device and there may be a hardware or communication issue. If the

condition is “ok,” the hardware is functioning normally.

Power Failure Status

This column displays the total number of Power Failures and the

date/time of the last occurrence, since it was last reset. In this

example, there were more than 15 power failures and the last time

occurred on 12/30 at 15:44.

Tamper Alarm

This column displays an active flag when a door is open on

the recorder. If the Tamper Alarm is not on, the column will display

.

O’Load (Over Load)

This column displays an overload flag when the meter has

excessive amperage (i.e. 200 amp load through the sensors on a 100

amp meter). When no problem exist the column display .

Power

This column displays any general power/voltage errors with the

meter (i.e. low, noisy or unstable). Low = voltage drop below

nominal level, noisy = dirty power supply, harmonics) unstable =

fluctuating levels. When no problems exist, the column displays

.

MTR Reg

This column displays any malfunctions with the recorder real-time

clock (i.e. ). When no problems exist, the column displays

.

IDR State

This column will display any problems that may exist with the

functionality of the IDR. When no problems exist, the column

displays