Pneumatic module, Configuration and function, Technical data – Burkert Type 8645 User Manual
Page 96: General technical data, Pneumatic data, General technical data pneumatic data, Config�uration and function, Configuration and function of the modules english
96 - 8645
ConfiGuraTion anD funCTion of The moDules
English
PNEuMATIc MOduLE
config�uration and Function
The pneumatic module performs pneumatic functions.
Two valves each of types 6524, 6525 or 0460 can be integrated
into the module.
Illustration: Pneumatic module
Technical data
General Technical data
Operating voltage
24 V -15 % / +20 %
Current consumption per valve function
(at 24 V)
During pick-up (
≤120 ms)
lowered
≤60 mA
≤25 mA
Pneumatic connections
D4, D6, D 1/4”
Material
PBT
Weight
with /2 or 5/2-way valves
with 2 x /2-way valves
12 g
14 g
Pneumatic data
valve type
6524
3/2-way
6525
5/2-way
6524
2 x 3/2-way
0460
5/2-way pulsed,
5/3-way
Method of operation
1)
C/D
H
2 x C
H pulsed, L, N
Nominal size [mm]
4
2.5
QNn
2)
[l/min]
00
200
Opening time
)
10 % [ms]
12
15
Closing time
)
10 % [ms]
20
H = 15 / L, N = 20
Pressure range
4)
[bar]
2.5 to 7
Vacuum to 7
Vacuum to 10
2.5 to 7
Vacuum to 7
Vacuum to 10
2.5 to 7
1 to 7
Vacuum to 10
2 to 7
Output [W]
1
1
2
0.9
Output [W]
after pick-up time (<120 ms)
1/4
1/4
1/2
1/4
Displays
1 LED per valve function
1)
C=NC (normally closed), D=NO (normally open), L=APB (all parts blocked), N=APO (all parts open)
2)
Flow rate QNn value air [l/min]: Measured at +20 °C, pressure 6 bar at valve entry and 1 bar pressure difference
)
Switching times [ms]: Measured to ISO 12238
4)
Pressure data [bar]: Overpressure with respect to atmospheric pressure