Operating and display elements, Rotary encoder switch, Led status displays – Burkert Type 8645 User Manual
Page 34: Operating� and display elements, Configuration and function of the modules english
4 - 8645
ConfiGuraTion anD funCTion of The moDules
English
Operating� and display Elements
Rotary Encoder Switch
(x10)
(x1)
Location: The rotary encoder switch is located in the lower part of
the Fieldbus module PROFIBUS
®
(see illustration Rotary encoder
switch).
Address setting Address 1 0 (x10) + 1 (x1)
: : :
Address 99 9 (x10) + 9 (x1)
Illustration: Rotary encoder switch
LEd Status displays
BUS_OK (BO)
FAILURE_SELECT (FS)
U_LOGIC_OK (U
l
)
U_SENSOR_OK (U
S
)
BUS_FAULT (BF)
FAILURE_NUMBER (FN)
U_DRIVER_OK (U
O
)
Display during
normal operation
BUS (BO)
BUS (BF)
FS
FN
U
o
U
l
U
S
ON
OFF
OFF
OFF
ON
ON
ON
Illustration: Allocation of the LEDs on the Fieldbus module PROFIBUS
®
LED Status Displays
Abbrevation colour
Relevance
Explanation
BO
green
Bus OK
Bus communication active
BF
red
Bus ERROR
Bus FAULT
FS
yellow
FAILURE
SELECT
Defines the function of the LED FB:
FS lit: FN indicates the type of failure
FS not lit: FS indicates the failure number
FN
red
FAILURE
NUMBER
The number of flashing pulses indicates the failure type or
failure number, depending on the setting of FS.
U
I
green
U Logic OK
Voltage for logic supply,
inputs and bus interface OK
U
O
green
U Driver OK
Power supply for the outputs OK
U
S
green
U Sensor OK
Separate display of the voltage for the inputs