ConfiGuraTion anD funCTion of The moDules

English

8645 - 45

cANopen RuN LED

cANopen RuN LED

Device status

Description

Single flash

STOPPED

Fieldbus module is status STOPPED.

Blinking

PRE-OPERATIONAL Fieldbus module is status PRE-OPERATIONAL.

ON

OPERATIONAL

Fieldbus module is status OPERATIONAL.

cANopen ERROR LED

cANopen ERROR LED

Device status

Description

Remedy

OFF

no error

Device is ready for opera-
tions.

-

Single flash

Warning Limit

Fieldbus module has
detected a certain number
of transmission errors (war-
ning limit).

Check cable connections
and terminal resistors.
If necessary, reduce baud
rate or bus cable length.

Double flash

Guard Event
has occurred.

No guarding telegram was
received within the given
time (time out).

Check whether master
sends a guarding telegram
within the given time.

ON

Bus OFF

Fieldbus module has dis-
connected itself from the
bus due to a large number
of detected transmission
errors (Bus OFF).

Check the cable connec-
tions and terminal resistors.

If necessary, reduce baud
rate or bus cable length.
Restart the field bus mo-
dule.