Configuration and function of the modules english – Burkert Type 8645 User Manual
Page 45
ConfiGuraTion anD funCTion of The moDules
English
8645 - 45
cANopen RuN LED
cANopen RuN LED
Device status
Description
Single flash
STOPPED
Fieldbus module is status STOPPED.
Blinking
PRE-OPERATIONAL Fieldbus module is status PRE-OPERATIONAL.
ON
OPERATIONAL
Fieldbus module is status OPERATIONAL.
cANopen ERROR LED
cANopen ERROR LED
Device status
Description
Remedy
OFF
no error
Device is ready for opera-
tions.
-
Single flash
Warning Limit
Fieldbus module has
detected a certain number
of transmission errors (war-
ning limit).
Check cable connections
and terminal resistors.
If necessary, reduce baud
rate or bus cable length.
Double flash
Guard Event
has occurred.
No guarding telegram was
received within the given
time (time out).
Check whether master
sends a guarding telegram
within the given time.
ON
Bus OFF
Fieldbus module has dis-
connected itself from the
bus due to a large number
of detected transmission
errors (Bus OFF).
Check the cable connec-
tions and terminal resistors.
If necessary, reduce baud
rate or bus cable length.
Restart the field bus mo-
dule.